Distinctive features
- Fast operation: giving the “Fire” signal within 0,2 - 0,5 seconds from the moment of ignition;
- Interference immunity at the cut of the window with background light without giving the “Fire” signal: for scattered sunlight - to 5000 lux; for fluorescent lamps - to 2500 lux; for incandescent lamps - to 250 lux;
- The ability to detect smoldering fires by applying of forced modulation of the light flux;
- The possibility to conduct periodic remote check of sensors due to the built-in simulator of infrared radiation.
You can download the request form, fill it and send to our e-mail: This email address is being protected from spambots. You need JavaScript enabled to view it., This email address is being protected from spambots. You need JavaScript enabled to view it., or request a price list directly from the website:
You can download the request form, fill it and send to our e-mail: This email address is being protected from spambots. You need JavaScript enabled to view it., This email address is being protected from spambots. You need JavaScript enabled to view it., or make a request directly from the website:
1. Purpose
Flame sensor MDP is intended for the detection of fires and smoldering seats of fire by infrared radiation and the giving of a signal to the input of modular receive and control fire protection device PPKP-M (see the appropriate section of the catalog).
2. Specifications
№ |
Name |
Value |
1 |
Spectral sensitivity |
Infrared radiation with a length of wave from 3.5 to 5.0 µm |
2 |
Sensitivity to the flame of test seats of fire TP-5 and TP-6 according to GOST Р 50898-96 |
no less than 25 m |
3 |
Viewing angle of the sensor |
90° |
4 |
Permissible light at the cut of the window of the sensor, no more |
- from scattered sunlight 5000 lux; - from fluorescent lamps 2500 lux; - from incandescent lamps 250 lux; |
5 |
Electric power supply |
24 V ±2 V |
6 |
Temperature of operation |
from -30 to +50°С |
7 |
Degree of protection of the shell |
IP 68 |
8 |
Weight, no more |
1,0 kg |
9 |
Dimensions |
195х80х60 mm |
10 |
Operation period, no less |
10 years |