FGUP "The Federal center for
dual-use technologies "Soyuz"

The enterprise was founded in 1947

140090, Russia, Moscow region, Dzerzhinsky, Academica Zhukova str., 42
Fax:+7(495) 551‑11‑44
e-mail: soyuz@fcdt.ru; sector_ves@rambler.ru

Civil use products

Distinctive features

  • Modular design
  • Hot swap of modules
  • Event log for 5 years
  • PC readable event log
 
Get the price of PPKP-M

You can download the request form, fill it and send to our e-mail: This email address is being protected from spambots. You need JavaScript enabled to view it., This email address is being protected from spambots. You need JavaScript enabled to view it., or request a price list directly from the website:

Place an order for PPKP-M

You can download the request form, fill it and send to our e-mail: This email address is being protected from spambots. You need JavaScript enabled to view it., This email address is being protected from spambots. You need JavaScript enabled to view it., or make a request directly from the website:

CONTACTS: fax: +7 (495) 551-06-18; E-mail: This email address is being protected from spambots. You need JavaScript enabled to view it., This email address is being protected from spambots. You need JavaScript enabled to view it.

 

1. Purpose

  • receiving information from flame sensors MDP (see the appropriate section of the catalog);
  • formation of control signals for automatic fire extinguishing equipment;
  • status control of automatic fire extinguishing equipment;
  • control of light and sound fire alarm devices.

2. The main functions of the device

  • automatic control of alarm loops and starting lines ("norm", "short circuit", "breakage", "attention", "fire") with a mark of the date and time of the event;
  • automatic diagnostics and testing of flame detectors at predetermined time intervals;
  • record of service staff activities;
  • non-volatile memory for 400 events;
  • automatic activation of fire extinguishing installations in each direction at triggering of a couple of detectors at the protected area;
  • alarm and alert in case of fire.

3. Specifications

Name

Value

1

The number of directions under control

4

2

The number of detectors to monitor one zone

2

3

Power supply voltage

-220 V from the mains 50 Hz

4

Power consumed in the standby mode, including 8 sensors MDP

35 W

5

Weight of the device, no more

6 kg

6

Dimensions

450x320x130 mm